Etd
Thermal Decomposition Products Testing With 1,1,1,2,2,4,5,5,5 nonafluoro-4-trifluoromethyl pentan-3-one (C6 F-ketone) During Fire Extinguishing
公开可下载的内容
open in viewerThe thermal decomposition products (TDP) generated during fire suppression with 1,1,1,2,2,4,5,5,5 nonafluoro-4-trifluoromethyl pentan-3-one were studied using wet chemistry and FTIR. Small-scale testing was conducted in a 1.28-m3 (45-ft3) enclosure. The effects of fire size, agent discharge time, and agent concentration on TDP are reported. A comparison of the two methods is presented. In terms of magnitude and generation trends, the TDPs were found to be comparable to other in-kind halon alternatives.
- Creator
- 贡献者
- Degree
- Unit
- Publisher
- Language
- English
- Identifier
- etd-0106103-152708
- 关键词
- Advisor
- Defense date
- Year
- 2003
- Date created
- 2003-01-06
- Resource type
- Rights statement
- 最新修改
- 2020-12-10
关系
- 属于 Collection:
项目
Permanent link to this page: https://digital.wpi.edu/show/cr56n103j